1. Εισαγωγή
This manual provides essential information for the safe and efficient installation, operation, and maintenance of the Riello Gulliver BS1 1-Stage 16-52 kW Low NOx Gas Burner. Please read this manual thoroughly before attempting any procedures with the burner.
Proper installation, commissioning, and maintenance are crucial for the safe and optimal performance of this device. Adherence to all local and national regulations is mandatory.
2. Πληροφορίες Ασφάλειας
ΠΡΟΕΙΔΟΠΟΙΗΣΗ:
- Installation (gas/water), initial commissioning, and maintenance of this device must only be carried out by a qualified HVAC system mechanic in accordance with valid regulations and these instructions.
- Failure to comply with safety instructions can result in serious injury, property damage, or death.
- Ensure the work area is well-ventilated during installation and maintenance.
- Πάντα να αποσυνδέετε την παροχή ρεύματος πριν από οποιαδήποτε επισκευή ή συντήρηση.
Φυλάξτε αυτό το εγχειρίδιο σε ασφαλές μέρος για μελλοντική αναφορά.
3. Το προϊόν τελείωσεview
Image 1: Riello Gulliver BS1 1-Stage Gas Burner. This image shows the compact, red-cased burner unit with its metallic combustion head.
The Riello Gulliver BS1 is a single-stage monoblock gas burner designed for efficient heating applications. Key features include:
- Μονο-σtage monoblock design.
- Suitable for natural gas, convertible to LPG (liquefied petroleum gas).
- Fully automatic operation.
- Flame tube made of stainless steel, resistant to high temperatures.
- Single-phase electric motor, 230 V, 50 Hz.
4. Προδιαγραφές
Image 2: Technical drawing with dimensions and a table of specifications for various Gulliver models, including BS1.
| Παράμετρος | Αξία |
|---|---|
| Μοντέλο | Gulliver BS 1 |
| Τύπος | 911 Τ1 |
| Εύρος ισχύος | 16-52 kW |
| Power Stages | 1 |
| Διαστάσεις (ΠxΒxΥ) | 234 x 276 x 295 mm |
| Flame Tube Length | 70-116 χλστ |
| Flame Tube Diameter | 89 χλστ |
| Πιστοποίηση | CE-0085 AQ 0409 |
| βαλβίδα αερίου | MBDLE 055 |
| Σύνδεση | R 1/2 Inch Max. |
| Πίεση εισόδου | 65 mbar |
| Multibloc Gas Valve Features | Integrated components: Filter, Pressure Regulator, Gas Pressure Monitor (shuts off if minimum gas pressure is not met), Safety Valve, Single-stage Operating Valve with Ignition Gas Flow Control (fast opening) and slow opening of main gas volume. |
| Καλωδίωση | Ready for plug-in connection. |
| Φλάντζα | Pre-assembled connection flange to the burner. |
| Εγκρίσεις | Joint approval for burner and gas valve. |
5. Ρύθμιση και εγκατάσταση
The Riello Gulliver BS1 burner comes with a Multibloc Gas Valve and assembly and operating instructions. It is crucial that installation is performed by a qualified professional.
5.1 Έλεγχοι προεγκατάστασης
- Verify that the burner model matches the requirements of the heating appliance.
- Ensure all components listed in the delivery scope are present.
- Check for any visible damage to the burner or its components.
5.2 Mounting the Burner
Mount the burner securely to the boiler or heating appliance using the pre-assembled connection flange. Ensure a gas-tight seal according to relevant standards.
5.3 Συνδέσεις αερίου και ηλεκτρικού ρεύματος
- Connect the gas supply to the Multibloc Gas Valve (R 1/2 Inch Max. inlet pressure: 65 mbar).
- Perform a gas leak test after connection.
- Connect the burner to a 230 V, 50 Hz single-phase electrical supply. The burner is supplied ready for plug-in connection.
- Εξασφαλίστε τη σωστή γείωση.
5.4 Αρχική θέση σε λειτουργία
Initial commissioning must be performed by a qualified technician. This involves:
- Adjusting the burner for optimal combustion based on the heating appliance's requirements.
- Checking all safety devices and controls.
- Verifying proper flame detection and ignition sequence.
6. Οδηγίες λειτουργίας
The Riello Gulliver BS1 burner operates automatically once properly installed and commissioned. Users should be aware of the following:
6.1 Starting the Burner
- Ensure the heating system is filled and vented.
- Turn on the main power supply to the burner.
- Set the thermostat or control system to demand heat. The burner will initiate its automatic start-up sequence.
6.2 Shutting Down the Burner
- To temporarily stop operation, lower the thermostat setting or turn off the heating demand.
- For extended shutdown or maintenance, turn off the main power supply to the burner at the dedicated switch.
- For complete system shutdown, close the main gas supply valve.
6.3 Ένδειξη σφάλματος
The burner is equipped with a control box that indicates operational status and potential faults. Refer to the detailed operating instructions provided with the burner for specific error codes and their meanings.
7. Συντήρηση
Regular maintenance is essential for the safe, efficient, and long-lasting operation of your Riello Gulliver BS1 burner. Maintenance must be performed by a qualified HVAC system mechanic.
7.1 Ετήσια Συντήρηση
- Combustion Analysis: Check and adjust combustion parameters (CO2, O2, CO, flue gas temperature) to ensure optimal efficiency and low emissions.
- Burner Head and Flame Tube Cleaning: Inspect and clean the burner head, flame tube, and ignition electrodes to remove any soot or deposits.
- Fan and Air Inlet Cleaning: Clean the fan impeller and air inlet grilles to ensure proper airflow.
- Gas Valve Inspection: Check the gas valve and associated components for proper operation and leaks.
- Ηλεκτρικές συνδέσεις: Ελέγξτε όλες τις ηλεκτρικές συνδέσεις για στεγανότητα και σημάδια φθοράς.
- Συσκευές ασφαλείας: Test all safety devices, including the gas pressure monitor and flame sensor.
7.2 User Checks (Daily/Weekly)
- Observe the burner's operation for any unusual noises or smells.
- Check the pressure gauge on the heating system.
- Ensure the area around the burner is clear of obstructions and flammable materials.
8. Αντιμετώπιση Προβλημάτων
If the burner malfunctions, consult the detailed troubleshooting guide in the original operating instructions. Below are some common issues and general advice:
| Πρόβλημα | Πιθανή αιτία | Δράση |
|---|---|---|
| Ο καυστήρας δεν ξεκινά | No power supply, thermostat not calling for heat, safety lockout, gas supply off. | Check power, thermostat setting, gas valve. Reset burner if in lockout (refer to manual). If problem persists, contact a qualified technician. |
| Ο καυστήρας ξεκινάει αλλά μπλοκάρει γρήγορα | No flame detected, insufficient air/gas mixture, faulty ignition. | Do NOT attempt to fix yourself. This requires a qualified technician to inspect and adjust the burner. |
| Ασυνήθιστος θόρυβος ή μυρωδιά | Combustion issues, mechanical fault, gas leak. | Immediately shut off gas supply and power. Ventilate the area. Do NOT attempt to restart. Contact emergency services and a qualified technician. |
For any issues beyond simple checks, always contact a qualified and certified HVAC technician. Do not attempt repairs yourself.
9. Εγγύηση και υποστήριξη
For warranty information, please refer to the documentation provided at the time of purchase or contact your seller. Riello products are known for their quality and reliability.
For technical support, spare parts, or service, please contact your authorized Riello dealer or a qualified HVAC system mechanic. Ensure to provide the model number (71300) and serial number of your burner when seeking support.
You can find more information and contact details on the official Riello webτοποθεσία: www.riello.com